CAT C9 ACERT 200 ekW/ 250 kVA/ 50 Hz/ Generator
CAT C9 ACERT 200 ekW/250 kVA/50 Hz generator is a product that stands out with its powerful performance and high efficiency. With a power output of 200 ekW/250 kVA, it is an ideal option to meet your electrical energy needs. The generator operates at a frequency of 50 Hz, has a motor speed of 1500 rpm, and provides a voltage of 400 V. For your short-term project requirements, you can contact us to get support from our rental options.
The CAT C9 ACERT is notable for its low fuel consumption and offers economical performance even when operating with a fan. The generator can work efficiently in a wide load range and provides fuel consumption values at 100%, 75%, 50%, and 25% loads.
The CAT C9 ACERT generator is designed in compliance with international standards and codes. With its durable structure and reliable performance, it is suitable for long-term use. This generator is an ideal backup power source for power outages and a reliable energy solution in industrial and commercial areas.
- Description
- Technical Specification
- DOCUMENTS & BROCHURES
Description
CAT C9 ACERT generator, with its high performance and low fuel consumption, is notable. This generator operates at 200 ekW/250 kVA and 50 Hz, with a motor speed of 1500 rpm and a voltage of 400 V with a power factor of 0.8.
The fuel consumption of the generator in fan operation is as follows:
– At 100% load: 51.9 L/hour (13.7 gal/hour)
– At 75% load: 40.0 L/hour (10.6 gal/hour)
– At 50% load: 28.9 L/hour (7.6 gal/hour)
– At 25% load: 18.2 L/hour (4.8 gal/hour)
The cooling system of the generator operates with a motor coolant capacity of 13.9 L (3.7 gal). The combustion air intake into the engine is 15.1 m³/min (533.3 cfm), and the maximum allowable combustion air inlet temperature is determined as 45°C (112°F).
The exhaust system has an exhaust gas temperature of 469.7°C (877.4°F) and an exhaust gas flow rate of 38.8 m³/min (1370.5 cfm). The maximum allowable exhaust system back pressure is determined as 10.0 kPa (40.0 in. water).
The generator’s alternator has a motor starting capacity of 465 skVA and an operating current of 361 amps. The frame size of the alternator is LC5014H, and it has an SE type regulation. The temperature rise is 130°C.
The emission values (nominal) are as follows:
– NOx: 4241.0 mg/Nm³ (9.0 g/hp-hr)
– CO: 702.5 mg/Nm³ (1.5 g/hp-hr)
– HC: 14.8 mg/Nm³ (0.0 g/hp-hr)
– PM: 30.1 mg/Nm³ (0.1 g/hp-hr)
The CAT C9 ACERT generator is designed in compliance with standards such as AS1359, CSA C22.2 No100-04, UL142, UL489, UL869, UL2200, NFPA37, NFPA70, NFPA99, NFPA110, IBC, IEC60034-1, ISO3046, ISO8528, NEMA MG1-22, NEMA MG1-33, 2006/95/EC, 2006/42/EC, 2004/108/EC.
The CAT C9 ACERT generator is designed for providing backup power in case of outages and has a capacity to generate 200 ekW of power. The average power output is 70% of the standby power rating. Typically, it is expected to be used for 200 hours per year, with a maximum usage time of 500 hours.
The CAT C9 ACERT generator is a suitable option for reliable performance and meeting energy needs.
Technical Specification
Genset Power Rating with Fan @ 0.8 Power Factor | 200 ekW |
---|---|
Genset Power Rating | 250 kVA |
100% Load with Fan | 51.9 L/hr, 13.7 gal/hr |
Engine Coolant Capacity | 13.9 L, 3.7 gal |
Combustion Air Inlet Flow Rate | 15.1 m³/min, 533.3 cfm |
Max. Allowable Combustion Air Inlet Temp | 45 °, C 112 ° F |
Exhaust Stack Gas Temperature | 469.7 ° C, 877.4 ° F |
Exhaust Gas Flow Rate | 38.8 m³/min, 1370.5 cfm |
Exhaust System Backpressure (Maximum Allowable) | 10.0 kPa, 40.0 in. water |
Motor Starting Capability @ 30% Voltage Dip | 465 skVA |
Current | 361 amps |
Frame Size | LC5014H |
Excitation | SE |
Temperature Rise | 130 ° C |